General information
- Two to eight loop or two to 16 loop versions
- Multiple protocols supported
- 500mA loop current
- Four programmable sounder circuits each rated at 2.5A – 5.25A or 10.25A power supply options
- Enclosure options to suit 26Ah or 45Ah battery options
- Three programmable inputs
- Five programmable relay outputs
- Up to 512 programme Input/Output via optional plug in and serially connected expansion cards
- Hard-wired fire and fault routing inputs and outputs
- Over 4000 sub address points per panel
- Option to ‘invert’ inputs and outputs
- Network up to 32 panels (approval for networks of up to 127 panels pending)
- Configurable via a USB flash drive or alternatively a PC USB serial connection
- Optional Media Gateway communications card
- Compatible with Ockular management solution
- Approved and compliant with EN54-2, EN54-4. EN54-part 13
- VdS approved
Use Taktis with